Delfield f15pc48n Instrução De Instalação
F5 & F15 Series Service and Installation Manual
For customer service, call (800) 733-8829, (800) 733-8948, Fax (989) 773-3210, www.delfield.com
8
F5 & F15 Series Service and Installation Manual
9
For customer service, call (800) 733-8829, (800) 733-8948, Fax (989) 773-3210, www.delfield.com
Proper installation must provide
for air flow to and from the
condensing unit. Two louvers
are provided with the unit and
should be installed as shown.
An “air duct” should be constructed
from the air-intake louver to the
condenser. This is recommended to
prevent recirculation of discharge air.
COND.
DUCT
FRESH
AIR
DIS-
CHARGE
AIR
TOP
VIEW
Discharge air louver
may be located further
from fresh air louver,
or on the opposite side
of counter.
15.5"
39.4 cm
Louver cut-outs are 24"
by 15.5" (60.1 cm by 39.4 cm)
typical. Cut-outs are to begin
a maximum of 4.00" (10.2 cm)
from the counter-top.
Cut-out dimensions are the same
for the discharge louver.
24"
60.1 cm
24"
60.1 cm
12.00"
30.5 cm
minimum
24"
60.1 cm
Unit is designed to be operated with supplied louvered
panels for proper air flow. Failure to provide the proper air
flow will void the warranty.
CONDENSER AIR FLOW: 48" & 72” WIDE UNITS