Whirlpool WGD5700V Manual Do Utilizador

Página de 28
10
A
B
A.  Standard rear offset exhaust installation
B.  Left or right side exhaust installation 
(27" wide models only)
C.  Bottom exhaust installation (27" wide models only)
Alternate installations for close clearances
Venting systems come in many varieties. Select the type best 
for your installation. Two close-clearance installations are shown. 
Refer to the manufacturer’s instructions.
A
B
A.  Over-The-Top installation (also available with  
one offset elbow)
B.  Periscope installation
noTE: The following kits for close clearance alternate 
installations are available for purchase. Please see the 
“Assistance or Service” section of the “Dryer User Instructions.”
Over-the-Top Installation:
 
Part Number 4396028
Periscope Installation (For use with dryer vent to wall vent 
 
mismatch):
Part Number 4396037 - 0" (0 mm) to 18" (460 mm) mismatch
Part Number 4396011 - 18" (460 mm) to 29" (737 mm) 
mismatch
Part Number 4396014 - 29" (737 mm) to 50" (1270 mm) 
mismatch
Special provisions for mobile home installations:
The exhaust vent must be securely fastened to a noncombustible 
portion of the mobile home structure and must not terminate 
beneath the mobile home. Terminate the exhaust vent outside.
 
C
D
Determine vent path:
Select the route that will provide straightest and most direct  
 
path outdoors.
Plan the installation to use the fewest number of elbows and 
 
turns.
When using elbows or making turns, allow as much room  
 
as possible.
Bend vent gradually to avoid kinking.
 
Avoid 90° turns when possible.
 
Determine vent length and elbows needed for best 
drying performance:
Use following Vent system chart to determine type of vent 
 
material and hood combinations acceptable to use.
noTE: Do not use vent runs longer than those specified  
in Vent system chart. Exhaust systems longer than those 
specified will:
Shorten life of dryer.
 
Reduce performance, resulting in longer drying times    
 
and increased energy usage.
The Vent system chart provides venting requirements that will 
help achieve best drying performance.
vent System Chart
number 
90° turns or 
elbows
Type of vent
Box/louvered 
hoods
Angled hoods
0
Rigid metal
64 ft. (20 m)
58 ft. (17.7 m)
1
Rigid metal
54 ft. (16.5 m)
48 ft. (14.6 m)
2
Rigid metal
44 ft. (13.4 m)
38 ft. (11.6 m)
3
Rigid metal
35 ft. (10.7 m)
29 ft. (8.8 m)
4
Rigid metal
27 ft. (8.2 m)
21 ft. (6.4 m)
noTE: Side and bottom exhaust installations for 27" wide 
models have a 90º turn inside the dryer. To determine maximum 
exhaust length, add one 90º turn to the chart.
vent System Chart (29" Wide long vent models only)
number 
90° turns or 
elbows
Type of vent
Box, louvered,  
or angled hoods
0
Rigid metal
120 ft. (36.6 m)
1
Rigid metal
110 ft. (33.5 m)
2
Rigid metal
100 ft. (30.5 m)
3
Rigid metal
90 ft. (27.4 m)
4
Rigid metal
80 ft. (24.4 m)
5
Rigid metal
70 ft. (21.3 m)