Connecting a Redundant Power Supply
27
Table 7 Power Availability
The unearthed 48V DC power distribution provides the mechanism to
connect to the Switch 5500. The distribution consists of a number of
circuit breakers and connection terminals for the positive (common) and
negative 48V outputs. Each Switch 5500 must be individually connected
to a circuit breaker terminal.
connect to the Switch 5500. The distribution consists of a number of
circuit breakers and connection terminals for the positive (common) and
negative 48V outputs. Each Switch 5500 must be individually connected
to a circuit breaker terminal.
A battery can also be connected to battery terminals prior to the DC
power distribution to provide uninterrupted power in order to protect
against the loss of AC mains power.
power distribution to provide uninterrupted power in order to protect
against the loss of AC mains power.
Specifying the
Redundant Power
System
For an approved vendor list, more details about purchasing the RPS and a
full set of requirements go to:
full set of requirements go to:
http://www.3Com.com/RPS
3Com’s redundant power solution allows the use of any off-the-shelf 48V
DC RPS that provides an ‘unearthed SELV’ output in compliance with IEC
60950-1/UL 60950-1/EN 60950-1, as defined in
DC RPS that provides an ‘unearthed SELV’ output in compliance with IEC
60950-1/UL 60950-1/EN 60950-1, as defined in
.
Connecting the
Switch to the
Redundant Power
System
When connecting the RPS to the Switch, the circuit breaker and 2-core
cable need to be matched to the power rating of the Switch.
cable need to be matched to the power rating of the Switch.
shows the recommended circuit breaker and cable rating for the Switch
5500. The recommended cable length should not exceed 3 metres (9.84
feet).
5500. The recommended cable length should not exceed 3 metres (9.84
feet).
Table 8 Switch 5500 Circuit Breaker and Cable Rating
Rectifiers
1
2
3
4
5
6
No Rectifier
Redundancy
Redundancy
1500W
3000W
4500W
6000W
7500W
9000W
N+1 Rectifier
Redundancy
Redundancy
-
1500W
3000W
4500W
6000W
7500W
Circuit Breaker
Minimum 2-Core Cable Diameter
Switch 5500 6A C type
18AWG (solid or stranded cable)