Eaton TPC2365-LT Manual Do Utilizador
© 2008 Eaton Corporation. All Rights Reserved. All specifications are subject to change without notice.
www.pulizzi.com • pulizzisales@eaton.com • 800-870-2248 • Fax: 605-334-4999
2
RACK MOUNTED
•
19” x 1U (1.72”) x 7”
•
Approximate shipping weight: 9 lbs.
•
TPC2365-2980 and TPC2365-3732
are 9.5” deep
are 9.5” deep
EMI/RFI FILTER
•
Differential Mode - Line to Line
•
Common Mode - Line to Ground
SPIKE/SURGE SUPPRESSION
•
Line to Line
IEC 60320 C20 Power Inlet
•
Power inlet is on the rear panel
•
Rated by UL/CSA at 125VAC/20A or
250VAC/16A Rated by TUV at
250VAC/16A Rated by TUV at
250VAC/16A
IEC 60320 OUTLETS (12)
•
Three sections of (4) switched outlets on
the rear panel. Each group of four
the rear panel. Each group of four
outlets are:
– Rated by UL/CSA up to 250VAC/15A
– Rated by VDE at 250VAC/10A
– Rated by UL/CSA up to 250VAC/15A
– Rated by VDE at 250VAC/10A
REMOTE SELECTION SWITCH
•
Local: Power “on or off” to the switched
outlets
outlets
•
Off: When breaker is “on” but this switch
is in the “off” mode, you will not have
power to the outlets
is in the “off” mode, you will not have
power to the outlets
•
Remote: Power “on or off” to the
switched outlets via a remote device
•
Latching remote on “LT” models only,
the selection switch is wired for
the selection switch is wired for
Remote/Off/Remote - There is no local
control
control
REMOTE INTERFACE
•
Remote on/off and EPO control - EPO
overrides remote and local control
overrides remote and local control
•
Sequence Power Up additional
equipment down line (standard on all units
equipment down line (standard on all units
•
Latching remote “LT” models only -
normally closed EPO, momentary start
MULTIPLE TIME DELAY (MTD™) (Optional)
•
Activated “Locally” or “Remotely”,
Section 1 powers up, followed
4-seconds later by Section 2 which is
followed 4-seconds later Section 3
then 4-seconds later the sequenced
4-seconds later by Section 2 which is
followed 4-seconds later Section 3
then 4-seconds later the sequenced
remote activates the next system in line
INDICATOR LIGHTS (5)
•
Power to Section 1, 2 and 3
•
115 VAC or 230VAC input selected
OVERLOAD CIRCUIT PROTECTION
•
Electromagnetic breaker provides manual
on/off switching and trips in an overload
condition
on/off switching and trips in an overload
condition
AUTO-VOLTAGE SELECTION
•
The AVS
TM
system automatically senses
the input voltage and adjusts the internal
components to use that voltage for the output
components to use that voltage for the output
SPECIFICATIONS
TPC2365
TPC2365/MTD
TPC2365-LT
TPC2365/LT
TPC2365-2980
TPC2365-3732
Approvals
cTUVus, CE
cTUVus, CE
cTUVus, CE
cTUVus, CE
NA
NA
Voltage Input/Output,
(50/60Hz)
(50/60Hz)
110-125V
200-240V
200-240V
110-125V
200-240V
200-240V
110-125V
200-240V
200-240V
110-125V
200-240V
200-240V
110-125V
200-240V
200-240V
200-240V
Current Input
20A
20A
20A
20A
30A
30A
Current Output
16A
16A
16A
16A
24A
24A
Full Load VA
1920VA / 3840VA
1920VA / 3840VA
1920VA / 3840VA
1920VA / 3840VA
2880VA / 5760VA
5760VA
Circuit Breaker
2 Pole 20A
2 Pole 20A
2 Pole 20A
2 Pole 20A
(3) 2 Pole 10A
(3) 2 Pole 10 A
Multiple Time Delay
NO
YES
NO
YES
YES
YES
EMI/RFI Filter
YES (20A)
YES (20A)
YES (20A)
YES (20A)
YES (30A)
YES (30A)
Surge Suppression
320V
320V
320V
320V
320V
320V
Outlets
IEC 60320
Type C13
Type C13
IEC 60320
Type C13
Type C13
IEC 60320
Type C13
Type C13
IEC 60320
Type C13
Type C13
IEC 60320
Type C13
Type C13
IEC 60320
Type C13
Type C13
Remote Control
Standard
Standard
Latching
Latching
Latching
Latching
Power Cable
Not Included
Not Included
Not Included
Not Included
10/3, 15’
10/3, 15’
Power Input
C20 Inlet
C20 Inlet
C20 Inlet
C20 Inlet
Bare Wire
L6-30P
TPC2365-LT Front
TPC2365-LT Front