Honeywell Liquid Cooled 25kW Home Standby Generator Guia De Especificação

Página de 6
3
KW RATING (LP/NG)
25/25
ENGINE SIZE
2.4 Liter Inline 4
GENERATOR OUTPUT VOLTAGE/KW - 60Hz
kW LPG
AMP
kW Nat. Gas
AMP
CB Size 
120/240V, 1-phase, 1.0 pf
25
104
25
104
125
120/208V, 3-phase, 0.8 pf
25
87
25
87
100
120/240V, 3-phase, 0.8 pf
25
75
25
75
90
ENGINE FUEL CONSUMPTION 
(Natural Gas) (Propane)
Natural Gas
(ft
3
/hr.)
Propane
 
(gal/hr.)
 
cu ft/hr
Exercise cycle
42
0.44
16
25% of rated load
108
1.2
44
50% of rated load
197
2.1
78
75% of rated load
287
3.1
114
100% of rated load*
359
3.9
143
  For Btu content, multiply ft
3
/hr x 2520 (LP) or ft
3
/hr x 1000 (NG)
ENGINE COOLING
Air flow 
(inlet air including alternator and combustion air)
 
ft
3
/min.
2,400
System coolant capacity
 
US gal.
3
Heat rejection to coolant
 
BTU/hr.
105,000
Max. operating air temp. on radiator
 
°C (°F)
60 (150)
Max. ambient temperature
 
°C (°F)
50 (140)
COMBUSTION AIR REQUIREMENTS
Flow at rated power 60 Hz
 
cfm
68
SOUND EMISSIONS IN DBA
Exercising at 7 meters
62
Normal operation at 7 meters
70
EXHAUST
Exhaust flow at rated output 60 Hz
 
cfm
180
Exhaust temp. at muffler outlet
 
°F
900
ENGINE PARAMETERS
Rated synchronous RPM
 
60 Hz
1800
POWER ADJUSTMENT FOR AMBIENT CONDIIONS
Temperature Deration                               3% for every 10 °C above - °C
1.65% for every 10 °F above - °F
25
77
Altitude Deration                                      1% for every 100 m above - m
3% for every 1000 ft. above - ft.
183
600
RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility 
source. The standby rating is applicable to varying loads for the duration of a power outage.  There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and 
specifications are subject to change without notice.
Operating Data
Refer to “Emissions Data Sheets” for maximum fuel flow for EPA and SCAQMD permitting purposes.