  Replacing a Power Filter Unit 
Removing the Failed PFU  ▀   
 
ASR 5000 Installation Guide  ▄  
 
   
221 
Removing the Failed PFU 
In the event of a PFU failure, follow these instructions to safely remove the PFU from the chassis. 
Step 1 
Power down the PFU by flipping the circuit breaker on the PFU to the OFF position. If the circuit breaker on your PFU 
is equipped with a locking clip, move the clip to the right to unlock the circuit breaker’s actuator. 
 
Step 2 
Shut down the power source to the failed PFU. 
W
ARNING
:
 To avoid the risk of electric shock, verify that the power source is completely shut down before 
proceeding to the next step.  Vor dem naechsten Schritt Spannungsversorgung abschalten, um einen elektrischen Schlag 
zu vermeiden. 
Step 3 
Use a Phillips #2 screwdriver to remove the plastic cover from the power terminals.