Replacing Application Cards    
▀  Determining Whether an Application Card has Failed 
 
 
▄  ASR 5000 Installation Guide 
240 
   
Determining Whether an Application Card has Failed 
The system has several ways to indicate an application card failure. The first indicator is that the Status LED on the 
System Management Card (SMC) turns red to indicate the failure of a chassis component. Another indicator is the 
Run/Fail LED on an application card is red or turns off if that card has a problem. 
If you see either of these indicators, you can determine the nature of the problem via the CLI or by checking the Simple 
Network Management Protocol (SNMP) traps. 
Using the CLI 
Monitor application cards in the chassis by executing the following CLI commands in Exec mode: 
show card diag slot_# 
slot_# is the chassis slot number in which the particular card that you wish to monitor is installed. For application cards, 
slot_# is any integer between 1 and 16. The following is a sample output for this command to monitor the card in 
chassis slot 8: 
Card 8: 
  Card Usable : Yes 
  Card Tests  : Pass 
  Boot Mode   : Normal 
show card info slot_# 
The following is a sample output for this command issued to monitor the card in chassis slot 8: 
Card 8: 
  Slot Type               : SMC 
  Card Type               : System Management Card 
  Operational State       : Active 
  Last State Change       : Thursday January 27 16:00:32 EST 2008 
  Administrative State    : Enabled 
  Card Lock               : Locked 
  Reboot Pending          : No 
  Upgrade In Progress     : No 
  Card Usable             : Yes 
  Single Point of Failure : No 
  Attachment              : 24 (System Processor I/O Card)  
  Attachment              : 25 (System Processor I/O Card)  
  Temperature             : 24 C (limit 101 C)  
  Voltages:               : Good 
  Card LEDs               : Run/Fail: Green | Active: Green | Standby: Off 
  System LEDs             : Status: Green | Service: Off 
  CPU 0                   : Kernel Running, Tasks Running 
If any of this information appears to be erroneous, such as the operational state or an LED state, check for any of the 
SNMP alarms listed in 
.