Technical Specifications   
▀  Power Requirements 
 
 
▄  ASR 5500 Installation Guide 
34 
   
Power Requirements 
Power Specifications 
The table below lists the power requirements for individual components of the ASR 5500 chassis. 
Table 6.  ASR 5500 Power Requirements 
Component
 
Parameter
 
Values
 
Notes
 
Chassis
 
Input voltage per feed circuit (nominal)
 
-48VDC
 
 
Input voltage per feed circuit (maximum)
 
-40VDC to -60VDC
 
 
Power feed circuits per each PFU
 
4
 
1
 
TUV rated peak current load per feed
 
80 amps @ -40 VDC
 
2
 
Maximum power load per chassis
 
12,800 watts
 
3
 
Cards
 
FSC
 
Maximum power
 
150 watts
 
 
SSC
 
Maximum power
 
10 watts
 
 
MIO or UMIO
 
Maximum power
 
650 watts
 
 
DPC or UDPC
 
Maximum power
 
630 watts
 
 
DPC2 or UDPC2
 
Maximum power
 
760 watts
 
 
Fan Tray Unit
 
Front
 
Maximum power
 
60 watts each (2 per chassis
 
 
Rear
 
Maximum power
 
940 watts each (2 per chassis)
 
 
 
Notes: 
1.  A minimum of four -48VDC power feeds are required on PFU-A to provide non-redundant power to a chassis 
and all its cards. Four additional power feeds are required on PFU-B for power redundancy (4+4 = 8). 
2.  Although the chassis may not draw 12.8 kW, a minimum of four 80-amp -48VDC feeds must be properly sized 
and wired to PFU-A to assure that all chassis slots are powered and available for future expansion. All power 
inputs on PFU-A must be connected to live power feeds to assure that all chassis card slots are energized. 
3.  The type and number of cards installed in the ASR 5500 chassis determine the actual -48VDC power draw. See 
  
Important:
  The power source must be a UL/CSA listed device with a regulated output no greater than -60VDC. 
 
Important:
  The DC power Battery Return (BR) or positive terminal, must be grounded at the source end (power 
feed or mains power end).