  Chassis Installation 
Grounding the Chassis  ▀   
 
ASR 5500 Installation Guide  ▄  
 
   
57 
Grounding the Chassis 
The chassis must be properly grounded prior to installing any chassis components or cards. The chassis and the 
equipment rack/cabinet must be connected to the same ground point. 
Caution:
  Failure to properly ground the chassis could result in personal injury and/or damage to the chassis and 
its components. 
There are two sets of grounding terminals located at the lower-rear of the chassis. Figure 4-8 shows the location of these 
terminals and provides specifications for the appropriate lug and cable size. 
Ground Cabling 
Important:
  The ASR 5500 is suitable for installation as part of the Common Bonding Network (CBN) in a 
network telecommunications facility. It is not intended for installation in an Isolated Bonding Network (IBN). 
A 2-hole lug (Panduit LCD4-14A-L) is supplied for grounding the chassis. The lug must be crimped to the end of a 
ground cable using Panduit crimp tool part number CT-720-1 (die color: gray, P29). The wire strip length is 7/8-inch 
(22 mm), 
The minimum, recommended stranded cable size is 4 AWG. the cable length to the site ground point should not exceed 
70 feet (21 m) one way. 
The method of connection is: chassis -> lug -> flat washer -> nut (7/16-inch).