Wall
<20mm
Plastic 
Anchor
Fixing the installation plate
2.  Fix the indoor unit.
(1)   Fix the installation plate to the wall giving attention to the weight of the indoor unit. 
(1)   Determine the positions of the wooden uprights to be 
attached to the window frame. 
(2)   Attach the wooden uprights to the window frame giving 
attention to the weight of the indoor unit.
(3)   Attach the installation plate to the wooden upright using 
tapping screws.
(1)   
(2)  Fix the plate hanger on two studs.
•   If you mount the plate to a concrete wall using plastic anchors, make sure that 
gaps between the wall and the plate, created by projected anchor, is less than 
20mm.
•   Search for other spots if there are less than two studs, or the distance between the studs are 
 from the 
plate hanger.
•  Fix the installation plate without inclining to one side.
•   Make sure that a wall can withstand the weight of the product. If you install the product in a place where it is not 
strong enough to withstand the product weight, the unit could fall and cause injury.
Connecting the assembly cable
•   Connect the power cable to the auxiliary circuit breaker. If every pole fails to connect to 
the power supply, it must be incorporated in a wire with a contact opening of ≥3mm.
Connecting the cable
If using a multi system, install as described in the installation manual supplied with the outdoor unit.
 Electrical work
1) For electrical and earth works, comply with the ‘technical standards of electrical installations’ and the 
2) Tighten the terminal block screw to under 12kgf.cm. 
3) Precautions when connecting terminal blocks of the indoor unit
 Before connecting, make sure the connecting part of the terminal socket is facing upwards.
the ‘wiring regulations’ of the Electricity Enterprises Act.
 
 
             
 
   
 
   
Upside down
There is no ring terminal
to cover the wire.
The terminal socket
is damaged.
Model
Power cable
Interconnection cable
Type GL 


18/24


12
3G, 2.5mm
² H07RN-F
3G, 1.0mm
² H05VV-F
4G
20A
, 1.5mm
² H07RN-F
3G, 1.0mm
² H07RN-F
25A
2, 0.75mm
² H05RN-F