Samsung AR12FSFKBWTX Manual Do Utilizador
36
Fixing the installation plate
Wall
<20mm
Plastic
Anchor
3. Fix the indoor unit.
If you fix the indoor unit on a wall
(1) Fix the installation plate to the wall giving attention to the weight of the indoor unit.
If you fix the indoor unit on a window frame
(1) Determine the positions of the wooden
uprights to be attached to the window frame.
(2) Attach the wooden uprights to the window
frame giving attention to the weight of the
indoor unit.
(3) Attach the installation plate to the wooden
upright using tapping screws.
If you fix the indoor unit on a gypsum board
(1) Use stud finder to find out locations of the studs.
(2) Fix the plate hanger on two studs.
• If you mount the plate to a concrete wall using plastic anchors, make sure that gaps
between the wall and the plate, created by projected anchor, is less than 20mm.
• Search for other spots if there are less than two studs, or the distance between the studs are different
from the plate hanger.
• Fix the installation plate without inclining to one side.
• Make sure that a wall can withstand the weight of the product. If you install the product in a place
where it is not strong enough to withstand the product weight, the unit could fall and cause injury.
Connecting the assembly cable
• Connect the power cable to the auxiliary circuit breaker. If every pole fails to connect to the
power supply, it must be incorporated in a wire with a contact opening of ≥3mm.
• Power supply cords of parts of appliances for outdoor use shall not be lighter than
polychloroprene sheathed flexible cord. (Code designation
IEC: 60245 IEC 66/CENELEC: H07RN-F,
IEC: 60245 IEC 57/CENELEC: H05RN-F)
Model
Power cable
(Outdoor Unit)
Power
Interconnection cable
(Indoor-Outdoor)
Type GL
AR09FSFKBWT/EE
AR12FSFKBWT/EE
AR12FSFKBWT/EE
3G, 2.5mm²
H07RN-F
Power Supply
3G,1.5mm², H07RN-F
15A
F1/F2
Communication
2G,0.75mm², H05RN-F
Cable specification
Connecting the cable
Electrical work
(1) For electrical and earth works, comply with the ‘technical standards of electrical installations’ and the the ‘wiring
(1) For electrical and earth works, comply with the ‘technical standards of electrical installations’ and the the ‘wiring
regulations’ of the Electricity Enterprises Act.
(2) Tighten the terminal block screw to 1.2 ~1.8 N•m (12 ~18 kgf•cm).
(3) Precautions when connecting terminal blocks of the indoor unit
Before connecting, make sure the connecting part of the terminal socket is facing upwards.
Upside down
The terminal
socketis damaged.
There is no ring
terminalto cover the wire.
There must be no space between the terminal and the screw when connected.
- Any remaining space may become a fire hazard due to overheating of the electrical contact.
The terminal socket
is upside down.
Either the screw is not fitted
properly or there is a space
between the screw and the
ring terminal.
Junfrau EE_AR09FSFK@_IB&IM_DB68-06190A-00_EN.indd 36
2016/5/5 13:34:29