•   Make sure the indoor unit is in upright position when you pour water to check for leakage.  
Make sure that the water does not overflow onto the electrical part. 
Change the direction only when it is necessary.
1.  Detach the rubber cap with the plier.
2.  Detach the drain hose by pulling it and turning to the left.
3.  Insert the drain hose by fixing it with the screw into the groove of the drain 
hose and the outlet of the drain pan. 
4.  Attach the rubber cap with a screwdriver by turning it to the right until it 
fixes to the end of the groove.
5.  Check for leakage on both side of the drain outlet.
Drain hose installation
Changing direction of the drain hose
Drain hose
Screw hole
Screw
Rubber cap
Drain pan outlet
Pour the water in direction of arrow.
 
Direction of the drained water
1.  If necessary, connect the 2-meter extension drain hose to the drain hose.
2.  If you use the extension drain hose, insulate the inside of the extension drain hose with a shield.
3.  Fit the drain hose into 1 of 2 drain hose holes, then fix the end of the drain hose tightly with a clamp.
4.     When extending the Drain Hose, hold the end of Drain Hose and Extended 
Hose, rotate and insert the drain hose into  Extended hose for 15~20 mm. Make 
sure the two hoses are firmly connected, there is no water leakage.
5.     Connect the Drain Hose after using Foam Insulation to wrap the Extended Hose. Then, Use vinyl tape to wrap the 
each side of connection by 20mm .
6.  Pass the drain hose under the refrigerant pipe, keeping the drain 
         hose tight.
7.  Pass the drain hose through the hole in the wall. Check if it slants 
downwards as seen in the picture.
8.     Using natural drainage method, check the drainage is normal.
Shield
Drain hose
Extension drain hose
•   If you do not use the other drain hose hole,
  block it with a rubber stopper. 
Drain hose hole
•   The hose will be fixed permanently into position after finishing the installation and the gas leak test; refer to page
45    for further details. 
•   Make sure the installed direction of the drain hose is correct. 
Inadequate installation may cause condensate water leakage.
•   If the drain hose is routed inside the room, insulate the hose so that dripping condensation does not damage the
furniture or floors.
•   DO NOT WALL UP THE DRAIN HOSE CONNECTION ! 
Drain hose connection must be easy accessible and serviceable. 
Drain hose Extension 
drain hose
Drain hose
Extension 
drain hose
40~45 mm
Foam Insulation
20 mm 
or more
20 mm 
or more
Vinyl Tape