Installing the Hardware
3
Items Required
Grounding wrist strap (included)
Phillips screwdriver
Flat-blade screwdriver
Serial cable
Site Preparation
Environmental Requirements
OmniSwitch 9000 Series switches have the following environ-
mental and airflow requirements:
The installation site must maintain a temperature 
between 0° and 45° Celsius (32° and 113° Fahrenheit) and 
not exceed 95 percent maximum humidity (non-condens-
ing) at any time.
Be sure to allow adequate room for proper air ventila-
tion at the front, back, and sides of the switch. Refer to 
 for minimum clearance 
requirements. No clearance is necessary at the top or 
bottom of the chassis.
Electrical Requirements
OmniSwitch 9000 Series switches have the following general 
electrical requirements:
Each switch requires one grounded electrical outlet for 
each power supply installed in the chassis. OmniSwitch 
9000 Series switches offer both AC and DC power supply 
support. Refer to the OmniSwitch 9000 Series Hardware 
Users Guide
 for more information.
For switches using AC power connections, each 
supplied AC power cord is 2 meters (approximately 6.5 
feet) long. Do not use extension cords.
Redundant AC Power. It is recommended that each AC 
outlet resides on a separate circuit. With redundant AC, if 
a single circuit fails, the switch’s remaining power 
supplies (on separate circuits) are likely to remain unaf-
fected and can, therefore, continue operating.
For switches using DC power, refer to the OmniSwitch 
9000 Series Hardware Users Guide for more information, 
including installation guidelines.
Installing the Hardware