Control a Device 7-15
Test the Parameter
A simple way to make sure that you have the correct configuration for
a parameter (data size, values, etc.) is to use the Class Instance editor
in RSNetWorx software.
a parameter (data size, values, etc.) is to use the Class Instance editor
in RSNetWorx software.
1. In RSNetWorx software, go online to
your DeviceNet network.
2. Right-click the device and choose Class
Instance Editor.
3. Type the class, instance, and attribute for
the parameter.
4. To change the parameter:
a. Choose Set Single Attribute.
b. Select the number of bytes.
c. Type the new value in hexadecimal format.
b. Select the number of bytes.
c. Type the new value in hexadecimal format.
5. To read the parameter, choose Get Single
Attribute.
6. Choose Execute.
7. To change how output data is displayed,
select the size and format.