Troubleshoot a DeviceNet Network 12-9
Ethernet (Network Status) status indicator
CIP Link status indicator
Module (Mod Status) indicator
State
Description
Recommended Action
off
Device has no IP address.
Give the device an IP address.
solid green
Device has at least 1 connection on the EtherNet/IP network. None.
flashing
green
green
Device has no connections on the EtherNet/IP network.
To use the device as a scanner, add it to the I/O configuration
of the controller.
of the controller.
solid red
The module’s IP address is already in use by another module. Change the IP address.
flashing
red
red
Communication with at least 1 device on the EtherNet/IP
network has timed out.
network has timed out.
1. Re-establish communication with the device.
2. Reset the module.
2. Reset the module.
red/green
alternate
flashing
alternate
flashing
A self-test of the module is in progress
None.
State
Description
solid green
EtherNet/IP I/O connection is active.
flashing green
Data is going between the networks.
State
Description
Recommended Action
flashing
green
green
• The device is not configured and is using default
values.
• The device is in a standby state. This could occur
during initialization or DeviceNet autobaud.
1. Configure the device.
2. Turn off autobaud.
2. Turn off autobaud.
solid green
Normal operation
None.
solid red
Device has an unrecoverable fault.
1. Cycle power to the device.
2. Replace the device
2. Replace the device
flashing
red
red
Recoverable fault.
Clear the fault.