Allen-Bradley devicenet modules in logix5000 control systems Manual Do Utilizador

Página de 239
Publication DNET-UM004A-EN-P - March 2004
Troubleshoot a DeviceNet Network        12-9
Ethernet (Network Status) status indicator
CIP Link status indicator
Module (Mod Status) indicator
State
Description
Recommended Action
off
Device has no IP address.
Give the device an IP address.
solid green
Device has at least 1 connection on the EtherNet/IP network. None.
flashing 
green
Device has no connections on the EtherNet/IP network.
To use the device as a scanner, add it to the I/O configuration 
of the controller.
solid red
The module’s IP address is already in use by another module. Change the IP address.
flashing 
red
Communication with at least 1 device on the EtherNet/IP 
network has timed out.
1. Re-establish communication with the device.
2. Reset the module.
red/green 
alternate 
flashing
A self-test of the module is in progress
None.
State
Description
solid green
EtherNet/IP I/O connection is active.
flashing green
Data is going between the networks.
State
Description
Recommended Action
flashing 
green
• The device is not configured and is using default 
values.
• The device is in a standby state. This could occur 
during initialization or DeviceNet autobaud.
1. Configure the device.
2. Turn off autobaud.
solid green
Normal operation
None.
solid red
Device has an unrecoverable fault. 
1. Cycle power to the device.
2. Replace the device
flashing 
red
Recoverable fault.
Clear the fault.