12-16        Troubleshoot a DeviceNet Network
Status Codes
Status codes give you detailed information about the status or error of 
the scanner or another device on the network.
• The status tags for the scanner give you the status codes. Refer 
• Some scanners also show status codes on the front of the 
scanner.
Use the following table to interpret status codes.
Status code 
(decimal)
Description
Action
65
The AutoScan option is on and the device is in 
idle mode.
None.
70
The address of the device is already in use by 
another device on the network.
Change the address of the device to an unused address.
71
Illegal data in scan list.
Reconfigure the scan list and remove any illegal data.
72
No communication with the device.
Inspect the device and verify connections.
73
Device’s identity information does not match 
electronic key in scanner
• Make sure that the correct device is at this address.
• Make sure that the device matches the specified electronic 
key (vendor, product code, product type).
74
Data overrun on port detected.
• Modify your configuration and check for invalid data.
• Check network communication traffic.
75
Either or both of the following:
• The device does not have a scan list.
• The device has not received 
communication from any other device
Check that the device has:
• scan list
• properly wired connection to the network
76
No direct network traffic for scanner.
None. The scanner hears other network communication but does 
not hear any directed to it.
77
During initialization, the data size expected by 
the device does not match the scan list entry.
Check the device and the scan list for the correct input and output 
size for the device.
78
Device is not communicating or communication 
is intermittent.
• Check that the device has a properly wired connection to the 
network.
• Check that the device has power.
• If the device is polled, make sure the interscan delay is long 
enough for the device to return its data.
79
Scanner has failed to transmit a message.
• Make sure that your scanner is connected to a valid 
network.
• Check for disconnected cables.
80
Scanner is in idle mode.
To run the network:
1. Put controller in run/remote run mode.
2. Turn on the following member of command register for the 
scanner:
…O.CommandRegister.Run