14-2 Using FLEX™ I/O Modules on a DeviceNet Network
Tally Memory
Requirements
Requirements
The Flex I/O adapter 1794-ADN packs the data of its I/O modules into
a contiguous block of input or output bytes. By default, the modules
share DINT elements in the scanner.
a contiguous block of input or output bytes. By default, the modules
share DINT elements in the scanner.
To determine the amount of scanner memory required for your
adapter and its I/O modules
adapter and its I/O modules
As an option, give each module its own memory location (DINTs)
within the scanner. This may make your programming easier. See Give
a Value Its Own Memory Location page A-1.
within the scanner. This may make your programming easier. See Give
a Value Its Own Memory Location page A-1.
Device
Input Size of
Device
(bytes)
Output Size
of Device
(bytes)
Flex I/O adapter—1794-ADN
2
0
digital output module—1794-OB16
2
2
digital input module—1794-IB16
2
2
Total
6
4
Device
Address
Input Size of
Device
(bytes)
Input Memory
in Scanner
(DINTs)
Output Size
of Device
(bytes)
Output Memory
in Scanner
(DINTs)
start/stop buttons
1
1
1
1
motor starter
4
1
4
1
Flex I/O adapter w/ modules
6
2
4
1
Total
1. Add the input bytes of each module + 2 bytes for the adapter.
2. Add the output bytes of each module (0 for
the adapter).
3. Add the totals to the main tally.
sub-tally
main tally