Allen-Bradley devicenet modules in logix5000 control systems Manual Do Utilizador

Página de 239
Publication DNET-UM004A-EN-P - March 2004
A-2        Give a Value Its Own Memory Location
Give a Value Its Own 
Memory Location
To give a value its own DINT in the input or output memory of the 
scanner:
1. Select the device and choose Advanced.
2. For the first map entry, specify 
the first bit of the data.
a. type of connection
b. starting byte of the data
c. starting bit of the data
3. Specify the map location for 
the data.
a. element number in the map
b. starting bit
c. number of bits
4. Apply the mapping.
5. Select the next map 
number.
7. Specify the map location for 
the data.
a. element number in the map
b. starting bit
c. number of bits
8. Apply the mapping.
6. Specify the first bit of the data 
for the next map entry for this 
device.
a. type of connection
b. starting byte of the data
c. starting bit of the data
9. Close when you are done.