Automatically Configure a DeviceNet Network        4-11
Put the Scanner in Run 
Mode
To run the DeviceNet network:
1. Place the controller in run/remote run mode.
2. Set the following bit of the output structure for the scanner:
3. Check the scanner for run mode:
If you want to:
The set this bit:
To:
run the network
…O.CommandRegister.Run
1
not run the network (idle mode)
…O.CommandRegister.Run
0
fault the network
…O.CommandRegister.Fault
1
not fault the network
…O.CommandRegister.Fault
0
disable the network
…O.CommandRegister.DisableNetwork
1
enable the network
…O.CommandRegister.DisableNetwork
0
halt the scanner (ceases all operation)
…O.CommandRegister.HaltScanner
1
unhalt the scanner
…O.CommandRegister.HaltScanner
0
reset the scanner 
…O.CommandRegister.Reset
1
resume operation after a reset
…O.CommandRegister.Reset
0
To put the scanner in run
mode, turn on this bit.
If you have this scanner:
Then this indicator:
Displays:
ControlLogix 1756-DNB
4-character display
RUN
FlexLogix 1788-DNBO
I/O
solid green