AEG 1000 Manual Do Utilizador
![AEG](https://files.manualsbrain.com/attachments/c3f563e4e34bb5664deffe95d65cd88c64c0016e/common/fit/150/50/c6e7a80bc8b4a26954dbeb57efd3ca22b652eb2636fb5dcffdee6743df05/brand_logo.png)
11
EN
2.3 Technical
Data
Type rating
PROTECT D.1000
1000 VA (pf = 0.9 lag.)
900 W
PROTECT D.1500
1500 VA (pf = 0.9 lag.)
1350 W
1350 W
PROTECT D.2000
2000 VA (pf = 0.9 lag.)
1800 W
1800 W
PROTECT D.3000
3000 VA (pf = 0.9 lag.)
2700 W
2700 W
UPS input
1ph~ / N / PE
Nominal input voltage
230 Vac
Rectifier voltage range
190 Vac – 276 Vac
(PROTECT D.1000 & D.1500)
200 Vac – 276 Vac
(PROTECT D.2000 & D.3000)
200 Vac – 276 Vac
(PROTECT D.2000 & D.3000)
Rectifier voltage range
180 Vac – 276 Vac
(PROTECT D.1000 & D.1500)
190 Vac – 276 Vac
(PROTECT D.2000 & D.3000)
190 Vac – 276 Vac
(PROTECT D.2000 & D.3000)
Rectifier voltage range
160 Vac – 276 Vac
(PROTECT D.1000 & D.1500)
180 Vac – 276 Vac
(PROTECT D.2000 & D.3000)
180 Vac – 276 Vac
(PROTECT D.2000 & D.3000)
Bypass voltage range
195.5 Vac – 253 Vac
Frequency
50 Hz / 60 Hz
(autom. recognition or manual)
(autom. recognition or manual)
Frequency tolerance range
± 5 Hz
Charging rate at full load and battery charging (max.)
PROTECT D.1000
4.8 A
PROTECT D.1500
7.2 A
PROTECT D.2000
9.6 A
PROTECT D.3000
13.7 A
Circuit feedback factor
λ > 0.99
(without battery operation
100% load, pf = 0.9 lag.)
(without battery operation
100% load, pf = 0.8 lag.)
(without battery operation
100% load, pf = 0.7 lag.)