act actpro mifare product range Manual Do Utilizador

Página de 4
ACTpro mifare 1050 Pin and Proximity Reader (Entry)
ACTpro mifare 1040 Proximity Reader (Exit)
Controller
SENSE
CLOCK
DATA
+5V
0V
RED
GREEN
CARD/PROX READER
2
3
1
5
6
4
8
9
7
0
White
Green
Blue
Red
Black
Brown
Yellow
Orange
No Connect
No Connect
SENSE
CLOCK / D1
DATA / D0
12V
0V
RED
GREEN
BUZZER
A
B
 
Wiring for Reader
The standard wiring colours for
ACTpro proximity and pin readers
is shown above.
125V
AC
30V
DC
+12V
 
0V
 
Data
 
C lock
Sense
 
R ed
Grn
B uzz 
Connection block view of ACTpro mifare 1040/1050.
Unit C1, S outh City Business Center, Tallaght, Dublin 24, Ireland. 
Telephone: +353 1 466 2570.  Telefax: 353 1 452 0427. E-mail: sales@ accesscontrol.ie  W eb: www.accesscontrol.ie
Wiring for Entry/Exit Readers
ACTpro mifare product range 
1040/1050
ACT
mifare
ACT
mifare
A
B
+1
2v
0
V
General Wiring information
READER MUST BE POWERED FROM 12vDC
ACTpro mifare
1040
Sector
No: 00005
Test
Powering on the reader requires 12V and 0V
to be Connected.
Data read from a card is presented on the
Data/Clock pins. If configured for wiegand
output the D0 signal is available on Data and D1
is available on Clock.
The Sense signal is driven low when the
reader outputs Clock and Data information, this
can be used to distinguish between Entry and
Exit (see below)
The Internal buzzer is activated by applying
0V to the Buzz. The buzzer activates 4 seconds
after the 0V is applied and sounds continuously
till the 0V is removed.
The Red/Green led is activated by applying 
0V to the respective Red/Grn input. 
READER MUST BE POWERED FROM 12vDC
To make a reader an exit reader leave the Sense line unconnected.
To make a reader an entry reader ensure the Sense line is connected.
Rev 1.3 27/04/2007
+1
2v
0
V
PAGE 1