Toshiba profibus-dp pbdp-110 Manual Do Utilizador

Página de 38
 
 21
Command Word 
Bit-mapped drive control command word (drive parameter number FA00).  This is the 
location where run/stop, etc. commands are written.  An example command word can 
be found in Table 1.  Because the format of this command word depends on the drive 
manufacturer’s specifications, please refer to your specific drive’s Serial 
Communications Manual
 for the exact structure of this word. 
 
Using the example command word in Table 1, some representative command words 
that can be used to control your drive via the Profibus network are: 
 
0xC400 ..........Profibus command valid, Profibus frequency valid, drive run forward 
0xC600 ..........Profibus command valid, Profibus frequency valid, drive run reverse 
0xC000 ..........Profibus command valid, Profibus frequency valid, drive stop 
0xE000 ..........Profibus command valid, Profibus frequency valid, reset drive fault 
 
Although the above examples all show Profibus command and frequency valid, input 
(status) data can always be monitored from the network regardless of the settings of 
bits 14 and 15 in the command word. 
 
 
Table 1 :  Example Command Word Format (S9 Drive) 
 
Bit Function 
15 Command 
source 
Local 
Network 
14  Frequency command source 
Local 
Network 
13 Fault 
reset 
N/A 
Reset 
12  Emergency OFF command 
N/A 
EOFF 
11  Coast stop command 
N/A 
Coast stop 
10  Run / stop command 
Stop 
Run 
Forward / reverse selection 
Forward 
Reverse 
H
ig
h B
yte
 
8 Jog 
command 
N/A 
Jog 
DC injection braking 
N/A 
DC injection cmd. 
Accel / decel #1/#2 selection 
#1 
#2 
5 Reserved 
-- 
-- 
4 Reserved 
-- 
-- 
Preset speed 4 
OFF 
ON 
Preset speed 3 
OFF 
ON 
Preset speed 2 
OFF 
ON 
Low Byt
Preset speed 1 
OFF 
ON