Toshiba VF-A7 Manual Do Utilizador

Página de 50
 
 29
 
Table 2 : Example Status Word (ASD Register 0xFE01) Format 
 
Bit Function 
15 Reserved 
-- 
14  Faulted status 
Not faulted 
Faulted 
13 Reserved 
-- 
12 Reserved 
-- 
11 Reserved 
-- 
10  Run / stop status 
Stopped 
Running 
Forward / reverse status 
Forward 
Reverse 
H
ig
h B
yte
 
Jog status 
Not jogging 
Jogging 
DC injection braking status 
Not DC injection 
braking 
DC injection 
braking 
Accel / decel #1/#2 status 
#1 
#2 
5 Reserved 
-- 
4 Reserved 
-- 
3 Reserved 
-- 
2 Reserved 
-- 
1 Reserved 
-- 
Low Byt
0 Reserved 
-- 
 
 
10.4  Register Remap Function 
Some Modbus client software does not allow access to more than 10,000 Modbus 
holding registers.  As the standard ETH-100 mapping provides a simple 1-to-1 
correspondence between Modbus holding registers and ASD registers (ASD register 
number + 1 = Modbus holding register number), this can cause certain critical ASD 
registers to be inaccessible from these clients.  Specifically, Toshiba drives typically 
place communication control registers and status registers in the 0xFAxx to 0xFFxx 
ASD register region.  For example, “Communication Frequency Command” is 
typically assigned to ASD register number 0xFA01, which is accessible via Modbus 
holding register 0xFA01 + 1 = 0xFA02, which is 64002 in decimal.  As this Modbus 
holding register number is higher than 10,000, this register would not be accessible 
via register-limited clients unless the ETH-100 performed register remapping. 
 
“Remap OFF” (default setting) does not modify the register mapping between the 
ASD registers and the Modbus holding registers: a simple 1-to-1 correspondence 
exists.  “Remap ON” modifies the ASD register mapping slightly to allow access to 
the drive’s critical control and status registers by Modbus clients that are limited to 
accessing 10,000 holding registers max. 
 
With the Remap parameter set to “ON”, the ETH-100 will add 0xF000 (61440
10
) to 
incoming ASD register accesses between 0x0A00 and 0x0FFF (Modbus holding 
registers 0x0A01 – 0x1000).  In this way, register-limited clients need only write to 
Modbus holding register 0x0A02 (2562
10
) to set the Communication Frequency 
Command.  Similarly, “Current Output Frequency” is typically located at ASD register