Cooling
 
fan
 
faults
 
 
Table
 
14.
 
Cooling
 
fan
 
faults
 
Symptom
 
Cause
 
Action
 
1.
   
Front
 
panel
 
fault
 
LED
 
amber
 
2.
   
Audible
 
alarm
 
sounding
 
3.
   
Fan
 
LED
 
is
 
illuminated
 
1.
   
Any
 
power
 
fault
 
2.
   
A
 
fan
 
failure
 
1.
   
Check
 
to
 
ensure
 
DC
 
power
 
to
 
cooling
 
fans
 
is
 
correct
 
and
 
that
 
the
 
LED
 
is
 
not
 
illuminated
 
2.
   
Disconnect
 
the
 
PSU
 
from
 
main
 
power
 
and
 
remove
 
the
 
faulty
 
fan
 
from
 
the
 
system.
 
Re-install.
 
If
 
problem
 
persists,
 
replace
 
PSU.
 
3.
   
Reduce
 
the
 
ambient
 
temperature
  
Thermal
 
cooling
 
The
 
Secure
 
Managed
 
Client
 
(SMC)
 
-
 
Storage
 
Array
 
uses
 
extensive
 
thermal
 
monitoring
 
to
 
ensure
 
component
 
temperatures
 
are
 
kept
 
low
 
and
 
acoustic
 
noise
 
is
 
minimized.
 
Airflow
 
is
 
from
 
front
 
to
 
rear
 
of
 
the
 
enclosure.
 
Table
 
15.
 
Thermal
 
cooling
 
Symptom
 
Cause
 
Action
 
If
 
the
 
ambient
 
air
 
is
 
cool
 
(below
 
25°C
 
or
 
77°F)
 
and
 
the
 
fans
 
are
 
observed
 
to
 
increase
 
in
 
speed
 
then
 
some
 
restriction
 
on
 
airflow
 
may
 
be
 
causing
 
an
 
additional
 
internal
 
temperature
 
rise.
 
Note:
 
This
 
is
 
not
 
a
 
fault
 
condition.
 
The
 
first
 
stage
 
in
 
the
 
thermal
 
control
 
process
 
is
 
for
 
the
 
fans
 
to
 
automatically
 
increase
 
in
 
speed
 
when
 
a
 
thermal
 
threshold
 
is
 
reached.
 
This
 
may
 
be
 
caused
 
by
 
higher
 
ambient
 
temperatures
 
in
 
the
 
local
 
environment
 
and
 
may
 
be
 
perfectly
 
normal.
 
Note:
 
This
 
threshold
 
changes
 
according
 
to
 
the
 
number
 
of
 
drives
 
and
 
power
 
supplies
 
installed.
 
1.
   
Check
 
the
 
installation
 
for
 
any
 
airflow
 
restrictions
 
at
 
either
 
the
 
front
 
or
 
rear
 
of
 
the
 
enclosure.
 
A
 
minimum
 
gap
 
of
 
2.5
 
cm
 
(1
 
inch)
 
at
 
the
 
front
 
and
 
5
 
cm
 
(2
 
inches)
 
at
 
the
 
rear
 
is
 
recommended.
 
2.
   
Check
 
for
 
restrictions
 
due
 
to
 
dust
 
build
 
up;
 
clean
 
as
 
appropriate.
 
3.
   
Check
 
for
 
excessive
 
re-circulation
 
of
 
heated
 
air
 
from
 
rear
 
to
 
front.
 
Use
 
in
 
a
 
fully
 
enclosed
 
rack
 
installation
 
is
 
not
 
recommended.
 
4.
   
Check
 
that
 
all
 
blank
 
modules
 
are
 
in
 
place.
 
5.
   
Reduce
 
the
 
ambient
 
temperature.
 
 
Chapter
 
5.
 
Troubleshooting
 
and
 
problem
 
solving
 
29