PowerFlex 40 and 400 Drive Control Logic
F232120
34
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Table 20 
Table 20 (continued)
Allen-Bradley Drive Fault Codes (continued)
Fault
Description
Corrective Action
Remarks
039
Phase V Fault
Phase to ground fault detected 
between controller and motor in 
Phase V.
Check wiring between the drive and motor. Check for 
grounded phase.
040
Phase W Fault
Phase to ground fault detected 
between controller and motor in 
Phase W.
Check wiring between the drive and motor. Check for 
grounded phase.
041
UV Short Fault
Excessive current has been 
detected between two controller 
output terminals.
Check motor and external wiring to the controller output 
terminals for shorted condition.
042
UW Short Fault
Excessive current has been 
detected between two controller 
output terminals. 
Check motor and external wiring to the controller output 
terminals for shorted condition.
043
VW Short Fault
Excessive current has been 
detected between two controller 
output terminals. 
Check motor and external wiring to the controller output 
terminals for shorted condition.
048
Reset to Default Values
Parameters were reset to the 
factory default values.
Verify or re-load the Alliance Laundry Systems specified 
parameters.
063
Software Over-current
Instantaneous (100 ms) trip based 
on ALS-specified maximum 
current setting.
Check for a locked motor or basket. Check for correct 
motor, basket and pulley combination. Check for an 
intermittent signal at the drive’s input terminals.
064
Drive Overload
The drive’s current rating has been 
exceeded by 150% for 1 minute or 
by 200% for 3 seconds.
Verify that the parameters are compatible with the motor 
and pulley combination. Check for a restriction in the 
basket’s rotation. Check for a poor or improper connection 
in the motor circuit.
100
Parameter Checksum
There is an internal checksum 
discrepancy.
Reset the drive’s parameters to the default factory settings 
and re-load the ALS-specified parameters.