Alliance Laundry Systems d355ie1b Manual Do Utilizador

Página de 88
504524
29
• Dryer unit exhaust duct should enter the main duct at an 
angle of no more than 30
°
 pointing in the direction of 
the air flow. Ducts entering the main duct from 
opposite sides should be staggered so as not to oppose 
each other. See illustration below.
• Provisions should be made for periodic lint removal 
and cleaning of the main collector duct.
• The outside end of the main duct should have a weather 
hood (with hinged dampers) installed to prevent 
passage of weather elements, insects, dust, and dirt into 
the dryer units.
• If a weather hood cannot be used, the outside end of the 
main duct should have a sweep elbow installed, and be 
directed downward as shown on the following page. If 
the main duct travels vertically through a roof rather 
than through a wall, install 180
°
 sweep elbow on the 
end of the duct with outlet at least 24 inches (61 cm) 
above the highest part of the building.
• Sufficient make-up air must be supplied to replace air 
exhausted from dryer units.
NOTE: Where the exhaust duct pierces the wall or 
ceiling, an opening having a diameter of 4 inches (10.2 
cm) larger than the diameter of the exhaust duct shall 
be provided, and the exhaust duct centered within the 
opening.
• Damper, Part No. 58786, should be installed in each 
dryer’s exhaust system. This will prevent a backdraft 
when dryer unit is not in use, and will keep the exhaust 
air in balance within the central exhaust system.
IMPORTANT: Provisions must be made for make-up 
air.
IMPORTANT: If several dryer units are exhausted 
into a main collector duct, it is essential that ductwork 
be adequate in size and properly constructed for 
efficient operation.
DRYER EXHAUST DUCT
DRYER EXHAUST DUCT
DRYER EXHAUST DUCT
DRYER EXHAUST DUCT
AIR FLOW
MAIN COLLECTOR DUCT
30
°
30
°
30
°
D026IE3A
30
°
To reduce the risk of fire and the 
accumulation of combustion gases, DO NOT 
exhaust dryer air into a window well, gas 
vent, chimney or enclosed, unventilated area, 
such as an attic, wall, ceiling, crawl space 
under a building or concealed space of a 
building.
W045
WARNING