Outdoor Unit
AVOID:
●
heat sources, exhaust fans, etc. (Fig. 2-1)
●
damp, humid or uneven locations.
DO:
●
choose a place as cool as possible.
●
choose a place that is well ventilated and outside
air temperature does not exceed maximum 115
°
F
constantly.
●
allow enough room around the unit for air intake/
exhaust and possible maintenance. (Fig. 2-2)
●
provide a solid base; about 6 inch above ground
level to reduce humidity and possible water damage
in the unit and decreased service life. (Fig. 2-3)
●
use lug bolts or equivalent to bolt down unit,
reducing vibration and noise.
In case of multiple installations
Fig. 2-1
Fig. 2-2
Min.
1 inch
1 inch
Min.
1 inch
1 inch
Min. 2 ft.
4 in.
0931_C_I
Min.
7 ft.
7 ft.
Ground
Air
dis-
charge
dis-
charge
0932_C_I
Obstacle above
Unit spacing if air discharge chamber is not used.
Unit spacing when air discharge chamber is used.
Min. 4 ft.
Min. 4 ft.
Min. 5 ft.
Min. 1 ft.
Min. 12 ft.
Min. 8 inch
Min. 4 ft.
Min. 8 inch
Min. 4 ft.
Min. 1 ft. 2 inch
Min. 1 ft. 2 inch
Min. 1 ft.
Min. 1 ft.
Air
discharge
chamber
discharge
chamber
If you would like to make the separation smaller on the air
discharge side, use an air discharge chamber.
You can install any number of units side-by -side.
discharge side, use an air discharge chamber.
You can install any number of units side-by -side.
Only up to 3 units can be installed side-by-side under the above
conditions. The next group must be spaced at least 1 ft. away
from the first group.
conditions. The next group must be spaced at least 1 ft. away
from the first group.
0933_C_S
Fig. 2-3
Air in
Air in
Air
discharge
discharge
Concrete block
4 inch
4 inch
×
1 ft. 4 inch
beams or equal
Anchor bolts
(4 pieces)
(4 pieces)
Min. 6 inch
0934_C_I