3. HOW TO INSTALL THE INDOOR UNIT
4-Way Air Discharge Semi-Concealed Type
(XH Type)
3-1. Suspending the Indoor Unit
This unit uses a drain pump. Use a carpenter’s level to
check that the unit is level.
3-2. Preparation for Suspending
(1)
 Fix the suspension bolts securely in the ceiling
using the method shown in the diagrams (Figs.
3-1 and 3-2), by attaching them to the ceiling
support structure, or by any other method that
ensures that the unit will be securely and safely
suspended.
(2)
Follow Fig. 3-2 and Table 3-1 to make the holes
in the ceiling.
(3)
Determine the pitch of the suspension bolts using
the supplied full-scale installation diagram. The
diagram and table (Fig. 3-3 and Table 3-2) show
the relationship between the positions of the
suspension fitting, the unit, and the panel.
32-9/32 (Ceiling opening)
Grille center
29-13/16 (Suspention bolt pitch)
X
1969_X_S
Refrigerant
tubing side 
Drain hose
side
B
(Suspention bolt pitch)
A (Ceiling opening)
Length
Type
Table 3-2
Unit : inch (mm)
A
B
C
D
E
XH1242XH1842, XH2442
6-3/16
7-5/32 10-9/32
12-1/8
4-7/8
(PNR-XH2442)
(157)
(182)
(261)
(308)
(124)
XH3642XH4242
6-3/16
7-5/32 11-15/32 13-1/16
4-7/8
(PNR-XH3632)
(157)
(182)
(291)
(338)
(124)
C
D
1-3/16
B
A
1970_X_S
E
Suspension lug
Refrigerant tubing joint (wide tube side)
Refrigerant tubing joint 
(narrow tube side)
Drain connection (another side)
(VP25)
Fig. 3-3
Table 3-1
Unit: inch (mm)
A
B
XH1242, XH1842 , XH2442
32-9/32 (820) 22-9/32 (566)
(PNR-XH2442)
XH3642, XH4242
43-11/16 (1,110) 33-11/16 (856)
(PNR-XH3642)