hearth-and-home-technolog cfx-crescent Manual Do Utilizador

Página de 38
Heat & Glo  •  CFX-CRESCENT  •  705-900  Rev. P  •  12/07
11
3
Installing the
Fireplace
Step 1
Locating the
fireplace
                                     Figure 2.   Fireplace Dimensions, Locations, and
                                                        Space Requirements
Clearance Requirements
The top, back, and sides of the fireplace are defined
by stand-offs.
Minimum Clearances from the Fireplace to
Combustible Materials
Glass
Rear
Sides of
Top of
Front
Floor
of Fireplace
Fireplace
Fireplace*
Ceiling*
36 inches
0
1/2 inch
1/2 inch
14 1/2 inches**
18 inches
(914mm)
(13mm)
(13mm)
(368mm)
(457mm)
The diagram below shows space and clearance
requirements for locating a fireplace within a room.
A
B
C
D
E
66 5/8
33 1/4
47 1/8
19 5/8
35 1/2
NOTE:  Dimensions shown in inches.
C
B
A
D
I INCH
  *  NOTE:  Add 1 3/8” to these measurements if measuring from the top of the door.
** NOTE:  2 x 4 framing only allowed at 43 5/8” (see Figures 3 and 26).
The minimum clearance to a perpendicular wall extend-
ing past the face of the fireplace is one inch (25mm).
The back of the fireplace may be recessed 19 1/4
inches (489mm) into combustible construction.
The distance from the unit to combustible construction is
to be measured from the unit outer wrap surface to the
combustible construction, NOT from the screw heads that
secure the unit together.