Gravely promaster 250z Manual Do Utilizador

Página de 44
 36
the wiring harness. Connections G and M open to each 
other.
START Position - Hold switch in START position while 
testing. There should be continuity between contacts 
S1 and S2. These connections apply power to close 
the solenoid contacts and operate the starter motor.
In addition to the above test, place the switch in the run 
position and check between each contact and ground 
(metal case) to be sure no terminals are grounded. If 
the switch is operating properly, there will be no 
continuity between contacts other that those described.
SOLENOID AND RELAYS
Solenoid and relays are both magnetically operated 
devices. Both devices operate on the principle that 
passing a current of electricity through a coil of wire will 
create a magnetic field strong enough to attract a piece 
of iron or steel. Each device uses this principle in a 
slightly different manner.
Relay - A basic relay consists of a coil of wire wound 
around a soft iron (magnetic) core. When current is 
passed through the coil, the core is magnetized and 
pulls down on a magnetic lever. The lever in turn is 
attached to several switch contacts which open or 
close other electrical circuits. In this fashion, a small 
current can control one or more larger electrical 
currents and actuate several other devices. In most 
cases a relay contact moves only a fraction of an inch 
and the magnetic pull is small.
Solenoid - A basic solenoid consists of a coil of wire 
wound around a hollow tube. A magnetic core slides 
inside the tube. When current is passed through the 
coil, the core is pulled into the solenoid with 
considerable force. With proper design, a solenoid can 
exert considerable force over a distance of several 
inched. A solenoid can therefore, pull a lever, close a 
heavy contact, or perform other jobs that require a 
straight line pull.
If a relay or solenoid fails to operate, the cause may be 
either electrical or mechanical.
To check electrically, connect a voltmeter across the 
coil of the device and activate the circuit that operates 
the relay or solenoid. If the meter indicates no voltage 
is applied, the cause is in the control circuit.
If the meter indicates proper voltage across the coil but 
the device does not function, remove the power, 
disconnect the wiring and check the continuity of the 
coil with an ohmmeter. The meter should indicate 
resistance, in the order of 3 to 5 ohms, if the coil is 
intact. A high resistance indicates an open coil and a 
defective device.
There are also a number of mechanical problems that 
may cause the problem.
The starter solenoid in the Ariens equipment is a 
sealed unit used to actuate the starter motor on the 
engines. These solenoids may have three or four 
connections. The two large connections carry high 
current to operate the starter motor. The small 
connections are connected to the coil and carry the 
control current.
To check the solenoid, disconnect the cables to the 
starter motor, turn the ignition switch to the start 
position, and listen for the solenoid to snap inside 
contacts closed.
If no snap is heard, check across the coils with a 
voltmeter. The voltage should read 12 volts with the 
ignition switch in the start position. If no voltage 
appears, the defect is in the start circuit.
If the voltage is correct, turn off the power and check 
continuity of the coil with an ohmmeter. If the coil is 
open, the solenoid is defective and must be replaced.
If the coil has the proper voltage applied, and the 
continuity check indicates the coil is intact, the solenoid 
plunger is stuck or the contacts are welded shut and 
the solenoid must be replaced.
If the solenoid snaps shut, but the start does not 
operate, check across the large contacts with an 
ohmmeter. If there is no continuity when the solenoid 
snaps shut, the contacts are defective and the solenoid 
must be replaced.
FUSES
Fuses are connected in electrical circuits to protect the 
circuits from damage due to overload or short circuits. 
Fuses are a "weak link" in the circuit. They contain a 
metal link designed to melt when a certain current 
value is exceeded thus opening or disconnecting the 
wiring. Once a fuse blows or melts it must be discarded 
and replaced with a new fuse of the same value.
Since the function of the fuse is to protect the circuit, 
NEVER attempt to defect the protective device by 
bridging or replacing with a device of a higher current 
rating.
Electrical testing of these devices is simple. Since the 
device either conducts current (and is therefore 
functioning) or the device is open and is therefore 
defective. Use an ohmmeter to check for continuity. 
DIODES AND RECTIFIERS
Diodes are solid state, semiconductor devices. They 
contain no moving parts and conduct current better in 
one direction than the other. They are electrical "check 
valves" and permit current flow in one direction, but not 
in the other. 
Diodes allow current to flow through one circuit without 
"backing up" into another. In engine alternator circuits, 
a diode is used to convert current which flows back and 
forth (AC) in a circuit to current which flows only in one 
direction (DC). A device which converts alternating 
current to a direct current is called a RECTIFIER. A 
diode is one type of rectifier.