Using Intelligent Output Terminals
Oper
ations
and Monitor
ing
4–28
The alarm output terminals are connected as shown below (left) by default. The contact 
logic can be inverted as shown (below right) by using the parameter setting C_33. The 
relay contacts normally open (N.O.) and normally closed (N.O.) convention uses 
“normal” to mean the inverter has power and is in Run or Stop Mode. The relay contacts 
switch to the opposite position when it is in Trip Mode or when input power is OFF.
N.C. contacts (after initialization)
N.O. contact (inverted by C_33 setting)
During normal running
When an alarm occurs 
or power is turned OFF
During normal running 
or power is turned OFF
When an alarm occurs
AL0
AL2
AL1
AL0
AL2
AL1
AL0
AL2
AL1
AL0
AL2
AL1
Contact
Power
Run 
State
AL0-
AL1
AL0-
AL2
N.C.
(after 
initialize, 
C_33=01)
ON
Normal
Closed
Open
ON
Trip
Open
Closed
OFF
Open
Closed
Contact
Power
Run 
State
AL0-
AL1
AL0-
AL2
N.O.
 (set 
C_33=00)
ON
Normal
Open
Closed
ON
Trip
Closed
Open
OFF
Open
Closed