Omron C200HG Manual Do Utilizador

Página de 564
352
When the execution condition is OFF, IOWR(––) is not executed. When the
execution condition is ON, IOWR(––) transfers data from the words beginning at
D to the specified Special I/O Unit’s memory. The destination information pro-
vides the node number of the Special I/O Unit and the number of words to be
written, as shown in the following diagram.
D:
Digits 2 to 4: Number of words to write (001 to 128)
Digit 1: Node number of the Special I/O Unit (0 to F)
The control code (C) depends on the Special I/O Unit being specified. Refer to
the Unit’s Operating Manual for details.
Example
When IR 00000 goes from OFF to ON, the following instruction writes the con-
tents of the 10 words from DM 0100 through DM 0109 to the memory area of
Special I/O Unit number 2.
IOWR(––)
C
DM 0100
#2010
00000
Address
Instruction
Operands
00200
LD
00000
00201
@IOWR(––)
C
DM
0100
#2010
Flags
ER:
The last three digits of D (number of words specifier) isn’t BCD or isn’t
within the range of 001 through 128.
Indirectly addressed DM word is non-existent. (Content of 
DM word is
not BCD, or the DM area boundary has been exceeded.)
The destination Unit’s unit number isn’t 0 to F or it is mounted on a Slave
Rack.
The instruction wasn’t completed normally.
EQ:
ON when the data was read successfully, otherwise OFF.
Description
Special I/O Unit Instructions
Section 5-29