Honeywell MS-9200UDLSE Manual Do Utilizador

Página de 188
Master Programming Level
Programming
MS-9200UDLS   PN 52750:A    11/04/05
105
24 Hour Test Time
Pressing 3 while viewing Primary/Secondary Screen #1 will cause the following 
screen to be displayed:
Use the 24 Hour Test Time screen to program the time that the DACT will transmit 
the 24 Hour Test to the Central Station.  A flashing cursor will appear in the lower 
left corner of the screen.  Enter a four digit number representing the test time using 
military time (0000 = midnight and 2359 = 11:59PM).
Phone Number
Pressing 1 while viewing Primary/Secondary Screen #2 will cause the following 
screen to be displayed:
The Phone Number screen is used to enter the Central Station phone number that 
the DACT will be contacting.  A maximum of 20 characters can be entered with 
valid entries being 0 - 9 and A - F where A = *, B = #, C = look for secondary dial 
tone for up to 2 seconds (then dial anyway), D = 3 second pause, E = 5 second pause 
and F = end of phone number (must be entered at end of phone number).  
A flashing cursor will appear in the lower left corner of the screen.  Enter the first 
digit then press the right arrow key to move the cursor to the right one position.  
Enter the second digit and repeat the process until all digits are entered.  Press the 
Enter key to store the phone number in memory.  
Enter the digits as you would like the number to be dialed.  For example, if it’s 
necessary to dial 9 before dialing a number outside the building, you may wish to 
pause after dialing 9.  Enter 9 followed by D for a three second pause or E for a five 
second pause then the phone number followed by an F to indicate the end of the 
number.
   CENTRAL STATION
1=TEST TIME INT
2=ACCOUNT CODE
3=24HR TST TIME
Primary/Secondary Screen #1
  24 HOUR TEST TIME
RANGE 0000-2359
24 Hour Test Time Screen  
   CENTRAL STATION
1=PHONE NUMBER
Primary/Secondary Screen #2
    PHONE NUMBER
20 NUMBERS MAXIMUM
Phone Number Screen