Pressing 2 while viewing the Program Check screen will display a screen similar to the 
following: 
The Zone No Input screen allows the programmer to view the zones which have not 
been programmed to at least one input device (not including general alarm Zone 00). 
The example in the preceding screen indicates that Zones 05, 07, 09, 10 and 11 have 
been programmed to an addressable module (control module in this example) with an 
address of 001 on loop 1 but have not been programmed to any input devices.  Use the 
up and down arrow keys to view all the zones without input assignments.
Pressing 3 while viewing Program Check screen will cause a screen similar to the 
following to be displayed:
The Zone No Output feature allows the programmer to view the zones which have not 
been programmed to at least one output device (not including general alarm Zone 00). 
The example in the preceding screen indicates that Zones 05, 07, 09, 10 and 11 have 
been programmed to an addressable detector with an address of 001 on loop 1 but have 
not been programmed to any output devices.  Use the up and down arrow keys to view 
all the zones without output assignments.
   ZONES NO INPUT
05 07 09 10 11 1M001
   ZONES NO OUTPUT
05 07 09 10 11 1D001