Operating Instructions
Special System Timers
138
MS-9200UDLS   PN 52750:A    11/04/05
4.20  Special System Timers
4.20.1  Silence Inhibit Timer
This option, if selected, prevents the Alarm Silence key from functioning for 60 seconds following 
an alarm.  A new alarm during the initial 60 second period will not cause the timer to restart with a 
new 60 seconds.  Silence Inhibit operation requires the approval of the local Authority Having 
Jurisdiction.
4.20.2  Autosilence Timer
If Autosilence is selected, the notification appliances, programmed as silenceable, will 
automatically be silenced after a programmable duration of from 5 to 30 minutes.  Pressing the 
Drill key will restart the timer.  Autosilence operation requires the approval of the local Authority 
Having Jurisdiction.
4.20.3  Trouble Reminder
If selected, this feature causes a reminding ‘beep’ every 15 seconds during an alarm (after the 
Alarm Silence key is pressed) and every two minutes during a trouble condition (after the 
Acknowledge/Step or Alarm Silence key is pressed).  The ‘beeps’ from the onboard piezo sounder 
will occur until the alarm or fault is cleared.
Note that if the trouble is not cleared within 24 hours, the piezo will resound, indicating that the 
trouble condition still exists.
4.20.4  Waterflow Retard Timer
If selected, this option will delay the activation of a waterflow type alarm for a programmable time 
duration from 1 to 90 seconds.  This delay is in addition to any time delay inherent in the waterflow 
device.  This feature requires the approval of the local Authority Having Jurisdiction.
!