Honeywell MS-9200UDLSE Manual Do Utilizador

Página de 188
Read Status
Operating Instructions
MS-9200UDLS   PN 52750:A    11/04/05
141
4.22.1  System Point 
Pressing 1 while viewing Read Status Screen #1 will cause the following screen to be displayed: 
The operator selects the type of device which is to be viewed by pressing 1 for Detector or 2 for 
Module.  If 1 is pressed, the display will change to the following screen:
Entering the three digit detector address will cause the control panel to display the current status of 
the selected device.  For example, if a detector with address 001 on the SLC loop is entered, a 
display similar to the following will appear:
The information in the preceding display includes:
• NORMAL - the present status (could also be ALARM, TROUBL, DISABL, etc.)
• SMOKE (PHOTO) - the device type which is a photoelectric smoke detector (could also be 
ION for ionization smoke detector)
• NORTH CLASSROOM - the Adjective/Noun label for this device
• Z005 - the first of five possible assigned software zones
• 1D001 - 1 = SLC Loop, D = Detector, 001 = Address 001
• V - Alarm Verification Enabled (V = Yes, * = No)
• S - Silenceable for control modules (S = Yes, * = No)
• W - Walktestable for control and monitor modules (W = Yes, * = No)
    READ STATUS
1=SYSTEM POINT
2=ZONES
3=POWER
Read Status Screen #1
 READ SYSTEM POINT
    SELECT TYPE
1=DETECTOR
2=MODULE
 READ SYSTEM POINT
ENTER DETECTOR#
***
NORMAL SMOKE(PHOTO)
    NORTH CLASSROOM
               Z005
            V   1D001