Honeywell MS-9200UDLSE Manual Do Utilizador

Página de 188
NFPA Standard-Specific Requirements
Correlations
174
MS-9200UDLS   PN 52750:A    11/04/05
APPENDIX C 
 
NFPA Standard-Specific Requirements
The 
MS-9200UDLS
 has been designed for use in commercial, industrial and institutional 
applications and meets the requirements for service under the National Fire Protection 
Association (NFPA) Standards outlined in this Appendix.  The minimum system 
components required for compliance with the appropriate NFPA standard are listed 
below:
MS-9200UDLS Control Panel
Contains the main control board, cabinet (backbox and door), main power supply 
transformer and power supply.
Batteries
Refer to  "Power Supply Calculations" on page 163, for Standby Power Requirements.
Initiating Devices
Connected to one of the control panel's Initiating Device Circuits.
Notification Appliances
Connected to the control panel's Notification Appliance Circuits via a control module.
The following additional equipment is needed for compliance with the NFPA 72 
standards listed below:
NFPA 72 NATIONAL FIRE ALARM STANDARDS FOR:
NFPA 72 Central Station Service (Protected Premises Unit) or Remote Station 
Service
Onboard Digital Alarm Communicator Transmitter for connection to a 
compatible listed Central Station DACR or Protected Premises 
Receiving Unit.  This unit must be installed as outlined in  "Digital 
Alarm Communicator/Transmitter" on page 17.
OR
4XTMF Transmitter Module for connection to the RS82 Remote Station 
Receiver.  See Figure C.2, “Remote Station Connection Using 4XTMF 
Module,” on page 176, for installation instructions for this unit.
NFPA 72 Auxiliary Fire Alarm System
F Transmitter Module for connection to a compatible listed Local Energy Municipal 
Box.  This unit must be installed as illustrated in the section titled  "4XTMF 
Transmitter Module Installation" on page 38 and as outlined in Figure C.1, “Municipal 
Box Connected to F Transmitter Module,” on page 175.
NFPA 72 Proprietary Fire Alarm System
MS-9200UDLS Alarm, Trouble and Supervisory contacts connected to Transmitter(s).  
See Figure C.3, “Proprietary Protective Signaling System,” on page 177, for installation 
instructions for this unit.