Power
Installation
MS-9200UDLS   PN 52750:A    11/04/05
31
2.3  Power
WARNING: Several different sources of power can be connected to this panel.  
Disconnect all sources of power before servicing.  The panel and associated equipment 
may be damaged by removing and/or inserting cards, modules or interconnecting 
cables while this unit is energized.
2.3.1  AC Power and Earth Ground Connection 
Primary power required for the FACP is 120 VAC, 
60 Hz, 3.0 amps for the MS-9200UDLS or 240 
VAC, 50 Hz, 1.5 amps for the MS-9200UDLSE.  
Overcurrent protection for this circuit must comply 
with Article 760 of the National Electrical Code 
(NEC) and/or local codes.  Use 14 AWG (2.00 
mm
2
) or larger wire with 600 volt insulation rating.  
Make certain that the AC mains circuit breaker is off before wiring any connections 
between the mains and the control panel.  Connect wiring from the AC mains to TB11 
on the FACP, being careful to observe proper connections. 
Connect a wire from the grounding stud in the cabinet to a known solid earth ground in 
the building.  Refer to Figure 2.1 on page 27 for location of the stud.  This connection is 
vital for maintaining the control panel’s immunity to unwanted transients generated by 
lightning and electrostatic discharge.  Apply AC power to the panel only after the 
system is completely installed and visually checked.  Note that AC power must be 
applied to the panel before installing the battery interconnect cable (refer to the 
following section).
2.3.2  Battery Power
Before connecting the batteries to the FACP, make 
certain that the interconnect cable between the 
batteries is not connected.  Do not connect the 
interconnect cable until the system is completely 
installed.  Observe polarity when connecting the batteries.  Connect the battery cable to 
J9 on the main circuit board.  Refer  "Power Supply Calculations" on page 163, for 
calculation of the correct battery rating.
WARNING: Battery contains sulfuric acid which can cause severe burns to the skin 
and eyes and can destroy fabrics.  If contact is made with sulfuric acid, immediately 
flush the skin or eyes with water for 15 minutes and seek immediate medical attention.
2.3.3  Special Application DC Power Output Connection
All Special Application DC power outputs are power-limited and require a ferrite bead 
per FCC requirements (refer to "UL Power-limited Wiring Requirements" on page 35). 
HOT  NEUT  EARTH
-  +
BATTERY
LCD DISPLAY
TB11
J1
J4
J9
-
-
+
+
Interconnect 
Cable
See Page
+   -   +   -
1
2
3
1    2    3    4
Figure 2.5 Special Application Power Outputs - 24 VDC
Power-limited Resettable or Nonresettable  Power
0.5 amperes max., 24 VDC nominal filtered, resettable 
or nonresettable power can be drawn from TB1 
Terminals 1(+) and 2(-)
Power-limited Resettable Power
0.5 amperes max., 24 VDC nominal filtered, resettable power can 
be drawn from TB1 Terminals 3(+) and 4(-)
92udtb1.cdr
JP4
TB1
JP4 is used to configure TB1, 
Terminals 1 & 2 for:
• Resettable Power - jumper pins 1 and 
2 of JP4 as shown
• Nonresettable Power - jumper pins 2 
& 3 of JP4