Honeywell MS-9200UDLSE Manual Do Utilizador

Página de 188
Programming
Programming Data Entry
42
MS-9200UDLS   PN 52750:A    11/04/05
SECTION 3
Programming 
3.1  Programming Data Entry
Programming can be accomplished using the MS-9200UDLS keypad or by connecting 
an optional standard computer keyboard.  The keyboard can be connected to the PS-2 
connector J3 on the control panel main circuit board.
The information presented in this section refers to programming the MS-9200UDLS 
via the onboard keypad.  If an optional computer keyboard is connected to the MS-
9200UDLS main circuit board, the following table describes the keyboard keys which 
correspond to the onboard keypad keys. 
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION 
AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software.  In order for the product to comply with the requirements in the 
Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must 
be limited to specific values or not used at all as indicated below:
Program feature 
or option
Permitted in 
UL 864? (Y/N)
Possible settings
Settings permitted 
in UL 864
Trouble Call Limit
N
Refer to  "Trouble Call Limit (Dialer Runaway Preven-
tion)" on page 102.
Trouble Call Limit = 0 (factory default): unlimited 
calling to Central Station for any trouble condition
Trouble Call Limit = 1 - 99: limits call for each unique 
trouble to from 1 to 99 within a 24 hour period
Trouble Call Limit 
= 0 for unlimited 
Central Station 
trouble calls
Keypad Keys
Computer Keyboard Keys
1st Event
Home
CLR
Delete
ESC
Esc
RECALL
Insert
*
*
#
#
A - Z
A - Z
0 - 9
0 - 9
 
(on QZ key)
Space bar
/
/
ENTER
Enter
ACK/STEP
F1
SILENCE
F2
DRILL
F3
RESET
F4