Honeywell MS-9200UDLSE Manual Do Utilizador

Página de 188
Master Programming Level
Programming
MS-9200UDLS   PN 52750:A    11/04/05
59
Pressing 1 for Control Module or 2 for Monitor Module will cause the following 
screen to be displayed:  
The programmer can continue adding modules by pressing the ESC or left arrow 
key which will return the display to the Add Module Screen #1. 
3.6.2.2.2  Delete Module
 Pressing 2 in the Modules Screen will display the Delete Module Screen which 
allows the programmer to delete a specific module: 
A flashing cursor will appear in the position of the first asterisk to the left.   Using 
the panel keypad, key in the module address such as 005.  When the last digit is 
keyed in, the following confirmation that the module has been deleted will be 
displayed: 
3.6.2.2.3  Edit Module Screen for Monitor Module
The programmer can change a modules existing or factory default programming by 
pressing 3 in the Modules Screen.  The following screen will be displayed: 
      ADD MODULE
MODULE#         005
IS ADDED
Add Module Screen #3  
MODULES
1=ADD
2=DELETE
3=EDIT
Modules Screen
  DELETE MODULE
ENTER MODULE#
***
Delete Module Screen  
  DELETE MODULE
MODULE#         005
IS DELETED
    EDIT MODULE
ENTER MODULE ADDRESS
***
Edit Module Screen