Honeywell MS-9200UDLSE Manual Do Utilizador

Página de 188
Programming
Master Programming Level
84
MS-9200UDLS   PN 52750:A    11/04/05
Pressing 3 while viewing Daylight Savings Screen #1 will display two sub-screens 
which allow the programmer to select the week of the month that daylight savings 
time will begin.  In the first sub-screen, pressing 1 will select the first week, 2 will 
select the second week and 3 will select the third week, while in the second sub-
screen, pressing 1 will select the fourth week and 2 will select the last week of the 
selected month.
Pressing 1 while viewing Daylight Savings Screen #2 will display another screen 
which allows the programmer to select the month that daylight savings time will 
end.  In this sub-screen, pressing 1 will select September, 2 will select October and 
3 will select November.
Pressing 2 while viewing Daylight Savings Screen #2 will display two sub-screens 
which allow the programmer to select the week of the month that daylight savings 
time will end.  In the first sub-screen, pressing 1 will select the first week, 2 will 
select the second week and 3 will select the third week, while in the second sub-
screen, pressing 4 will select the fourth week and 5 will select the last week of the 
selected month.
3.6.5.4  Timers
Timer delays for PAS, Pre-signal and waterflow activation can be programmed by 
pressing 1 while viewing System Setup Screen #2.  The following screen will be 
displayed: 
3.6.5.4.1  PAS (Positive Alarm Sequence) Delay
The factory default setting for PAS is 000 for no delay.  To select a PAS delay of 001 
to 180 seconds for all devices programmed for PAS, press 1 while  viewing Timer 
Screen #1.  The following display will appear: 
A flashing cursor is positioned in the lower left corner of the display.  Enter a delay 
time consisting of three digits, such as 005 for five seconds.  Upon entering the third 
digit, the time delay will be stored in the control panel memory and the display will 
return to the Delay Screen which will indicate the new delay time.
   SYSTEM SETUP
1=TIMERS
2=NAC
3=RELAYS
System Setup Screen #2
      TIMERS
1=PAS DELAY      000
2=PRE SIGNAL     000
3=WATERFLOW      000
Timer Screen #1  
      TIMERS
1=AC LOSS DELAY  000
Timer Screen #2  
   TIMERS
1=PAS DELAY   000
2=PRE SIGNAL  000
3=WATERFLOW   000
Timer Screen #1
     PAS DELAY
RANGE 0-180 SECONDS
PAS Delay Screen