Programming
Master Programming Level
102
MS-9200UDLS   PN 52750:A    11/04/05
3.6.9.2.5.2  Backup Reporting
The DACT can be programmed to transmit reports to primary and/or secondary 
central station phone numbers as a backup.  Press 2 while viewing Central Station 
Screen #1 to display the following screen:
Press 1 to have all reports transmitted to the central station secondary phone number 
as a backup only if the primary phone line fails, 2 to transmit all reports to both the 
primary and secondary phone numbers all of the time or 3 to send reports to the first 
available phone number.
3.6.9.2.6  Trouble Call Limit (Dialer Runaway Prevention)
The Call Limit option limits the number of DACT trouble calls to the Central 
Station, to a programmed amount between 0 and 99, for each unique trouble within 
a 24 hour period.  Separate limit counters keep track of each unique type of trouble.  
Note that the number of phone line (communication) faults called to the Central 
Station are not limited by this feature.  No subsequent restoral message is sent to the 
Central Station(s) for a particular trouble whose call limit has been reached.  Local 
DACT annunciation will still track the particular trouble and restoral.
To set the Trouble Call Limit, press 3 while viewing Central Station Screen #1.  The 
following screen will be displayed.
Enter a value between 00 and 99, then press Enter to set the Call Limit to this value.  
Note:  Entering a value of 00 will disable the Trouble Call Limit allowing the DACT 
to call the Central Station an unlimited number of times.
 BACKUP REPORTING
1=BACKUP ONLY
2=BOTH
3=FIRST AVAILABLE
Backup Reporting Screen  
 TROUBLE CALL LIMIT
  00-99 RANGE
*
Backup Reporting Screen