Programming
Master Programming Level
118
MS-9200UDLS   PN 52750:A    11/04/05
3.6.12  Program Check
The Program Check feature allows the programmer to view the zones which have been 
programmed to the Notification Appliance Circuits on the control panel but have not 
been programmed to Initiating Devices as well as other circuits with no input or output 
correlations.  Pressing 3 while viewing Programming Screen #4 will cause the 
following screen to be displayed:
Pressing 1 while viewing the Program Check screen will display an NAC screen similar 
to the following.
The example above indicates that NAC 1 has been programmed to Zones 25, 31, 44, 55 
and 67 but no input devices have been programmed to any of these zones.  Use the up 
and down arrow keys to view all the NAC zones without input assignments for NAC 1, 
NAC2, NAC 3 and NAC 4.
Note:  If the NACs have been configured for Class A in the Setup option, only NAC1 
and NAC 2 will display test information.  NAC 3 and NAC 4 will display asterisks (*) 
and will not be included in the test.
    PROGRAMMING
1=PASSWORD CHANGE
2=CLEAR PROGRAM
3=PROGRAM CHECK
Programming Screen #4
    PROGRAMCHECK
1=NACS NO INPUT
2=ZONES NO INPUT
3=ZONES NO OUTPUT
   PROGRAMCHECK
1=NACS NO INPUT
2=ZONES NO INPUT
3=ZONES NO OUTPUT
Program Check Screen 
   NACS NO INPUT
NAC 1
    25 31 44 55 67