Power Supply Calculations
Calculating the System Current Draw
164
MS-9200UDLS   PN 52750:A    11/04/05
7.3  Calculating the System Current Draw
7.3.1  Overview
The control panel must be able to power all internal and external devices continuously 
during the non-fire alarm condition.  To calculate the non-fire alarm load on the system 
power supply when primary power is applied, use Calculation Column 1 in Table 7.3 on 
page 165.  The control panel must support a larger load current during a fire alarm con-
dition.  To calculate the fire alarm load on the power supply, use Calculation Column 2 
in Table 7.3 on page 165.  The secondary power source (batteries) must be able to 
power the system during a primary power loss.  To calculate the non-fire alarm load on 
the secondary power source, use Calculation Column 3 in Table 7.3 on page 165.
When calculating current draw and the battery size, note the following:
• ‘Primary’ refers to the main power source for the control panel
• ‘Secondary’ refers to the control panel’s backup batteries
• All currents are given in amperes (A).  Table 7.2  shows how to convert milliam-
peres and microamperes to full amperes. 
7.3.2  How to Use Table 7.3 on page 165 to Calculate System 
Current Draw
Use Table 7.3 on page 165 to calculate current draws as follows:
1. Enter the quantity of devices in all three columns
2. Enter the current draw where required.  Refer to the Device Compatibility 
Document for compatible devices and their current draw
3. Calculate the current draws for each in all columns
4. Sum the total current for each column
5. Copy the totals from Column 2 and Column 3 to Table 7.4 on page 166
Following are the types of current that can be entered into Table 7.3 on page 165:
Calculation Column 1 - The primary supply current load that the control 
panel must support during a non-fire alarm condition, with AC power applied. 
Calculation Column 2 - The primary supply current load that the control 
panel must support during a fire alarm condition, with AC power applied.
Calculation Column 3 - The standby current drawn from the batteries in a 
non-fire alarm condition during a loss of AC power.
Table 7.2  Converting to Full Amperes
To convert...
Multiply
Example
Milliamperes (mA) to
amperes (A)
mA x 0.001
3 mA x 0.001 = 0.003A
Microamperes (
µ
A) to
amperes (A)
µ
A x 0.000001
300 
µ
A x 0.000001 = 0.0003 A