Product Description
Accessories
22
MS-9200UDLS   PN 52750:A    11/04/05
1.8.5  Annunciators
ACS Series LED Zone Type Annunciators
The ACS Series Annunciators remotely display alarm and trouble status as well as 
system status.  In addition, they can provide remote Acknowledge, Silence, Reset and 
Drill functions.  For more detailed information, refer to the appropriate annunciator 
manual.  Following is a list of annunciators which can be used with the MS-
9200UDLS.
• ACM-16ATF
*
 Annunciator Control Module annunciates 16 zones with 16 red 
alarm LEDs and 16 yellow trouble LEDs.  In addition, it has a System Trouble 
LED, an On Line/Power LED and a local piezo sounder.  It also has switches for 
FACP Acknowledge, Silence, Reset and Drill.  It has rotary address switches and 
will accept up to three AEM-16ATF Expanders.  In Canada, this module must be 
used to annunciate the fire alarm input points/zones only.
• AEM-16ATF Annunciator Expander Module annunciates 16 zones with 16 red 
alarm LEDs and 16 yellow trouble LEDs
• AFM-16ATF
*
 Annunciator Fixed Module annunciates 16 zones with 16 red 
alarm LEDs and 16 yellow trouble LEDs.  In addition, it has a System Trouble 
LED, an On Line/Power LED and a local piezo sounder.  It also has switches for 
FACP Acknowledge, Silence, Reset and Drill.  It is fixed at address ‘1.’  In 
Canada, this module must be used to annunciate the fire alarm input points/zones 
only.
• ACM-32AF
*
 Annunciator Control Module annunciates 32 alarm zones with 32 
red LEDs.  In addition, it has a System Trouble LED, an On Line/Power LED 
and a local piezo sounder.  It also has a switch for local piezo silence.  It has 
rotary address switches and will accept one AEM-32AF Expander.  In Canada, 
this module must be used to annunciate the fire alarm input points/zones only.
• AEM-32AF Annunciator Expander Module annunciates 32 alarm zones with 32 
red LEDs
• AFM-16AF
*
 Annunciator Fixed Module annunciates 16 alarm zones with 16 red 
alarm LEDs.  In addition, it has a System Trouble LED, an On Line/Power LED 
and a local piezo sounder.  It also has a switch for local piezo silence.  It is fixed 
at address ‘1.’  In Canada, this module must be used to annunciate the fire alarm 
input points/zones only.
• AFM-32AF
*
 Annunciator Fixed Module annunciates 32 alarm zones with 32 red 
LEDs.  In Canada, this module must be used to annunciate the fire alarm input 
points/zones only.
*  In Canada, the color red must be used to indicate active alarm inputs.  Yellow 
indicates supervisory, burglary or trouble signals.  Green indicates the presence of 
power, or an activated output.