Programming
Master Programming Level
52
MS-9200UDLS   PN 52750:A    11/04/05
Type
To select the type of detector being programmed, press the 2 key while viewing the 
Edit Detector Screen #2.  This will cause the control panel to display the following 
Detector Type Screens:   
Pressing the down arrow key will display additional detector types as indicated in 
the following table.
While viewing either Detector Type screen, select the type of detector being 
programmed by pressing the corresponding keyboard number key.  The display will 
return to Edit Detector Screen #2 and indicate the selection next to the Type option.
Note: If a detector is selected to be a SUPERV DUCTP type, it will function like a 
supervisory point not a fire alarm point.  The supervisory LED and supervisory 
relay will activate, not the fire alarm LED or alarm relay, if the detector senses 
smoke.
Verification
Alarm verification is used to confirm that a smoke detector activation is a true alarm 
condition and not a false alarm.  This feature is selected by pressing 3 while viewing 
the Edit Detector Screen #2 so that the display reads Verification On.  Each time the 
3 key is pressed, the display will toggle between Verification On and Verification 
Off
.  For a detailed description, refer to  "Alarm Verification (None or One Minute)" 
on page 139.
Walktest
The Walktest feature allows one person to test the system devices without the 
necessity of manually resetting the control panel after each device activation.  To 
enable a device for the Walktest feature, press 1 while viewing the Edit Detector 
Screen #3 until the display reads Walktest Yes.  Each press of the 1 key will cause 
the display to toggle between Walktest Yes and Walktest No.  Refer to  "Walktest" on 
page 139.
Detector Type
Action When Activated
Smoke Photo
Fire Alarm
User-Defined-1
same as previous (Smoke Photo)
Smoke Ion
Fire Alarm
User-Defined-2
same as previous (Smoke Ion)
Heat Detect
Fire Alarm
User-Defined-3
same as previous (Heat Detect)
Smoke DuctP
Fire Alarm
User-Defined-4
same as previous (Smoke DuctP)
Superv-DuctP
Supervisory, latching
User-Defined-5
same as previous (Superv DuctP)
Future
not used
Future
not used
EDIT DETECTOR
1=ENABLED
2=TYPE
3=VERIFICATION
Edit Detector Screen #2
   DETECTOR TYPE
1=SMOKE(PHOTO)
2=USER-DEFINED-1
3=SMOKE (ION)
Detector Type Screen #1  
See Page
EDIT DETECTOR
1=WALKTEST
2=PAS
3=PRE-SIGNAL
Edit Detector Screen #3