Programming
Master Programming Level
78
MS-9200UDLS   PN 52750:A    11/04/05
3.6.3.7  Zone Type
Zone Types must be programmed only if a DACT, programmed for zone reporting, 
is installed on the control panel.  Pressing 1 for Zone Types, while viewing Zone 
Setup Screen #3, will display a screen similar to the following: 
This display will show the system zones (default and user programmed) and their 
associated types.  Note that an up and/or down arrow will appear in the upper right 
corner of the display, indicating that additional screens of zone information exists.  
Press the up or down arrow keys to view zones Z00 through Z99.
Zone types can be changed by pressing the keypad number key corresponding to the 
zone in each Zones Installed Screen.  Available zone types will be displayed in the 
resultant screens.  For example, to change the zone type for zone Z02 in the screen 
illustrated above, press 3.  The following screens will be displayed: 
To change the zone type for Z02 to Pull Station, scroll the display until Zone Type 
Program Screen #2 is displayed.  Press 2 to program zone Z02 as a Pull Station 
zone.  The display will return to the Zones Installed Screen showing zone Z02 and 
the Pull Station program type.  Repeat the procedure for each zone to be changed.
IMPORTANT!  In Zone Type Program Screen #1, selecting WATERFLOW will 
assign a Waterflow silenceable zone type to the selected zone.  Any signaling 
devices programmed to the same zone can be silenced by pressing the Alarm Silence 
key or by using the auto-silence feature.  
To program a waterflow circuit as nonsilenceable, refer to  "System Setup" on page 
80.
Note:  Zone Types are only relevant for Central Station reporting.  Changing a zone 
type will only change how it is reported to the Central Station.
    ZONE SETUP
1=ZONE TYPES
2=ZONES AVAILABLE
3=ZONE MESSAGE
Zone Setup Screen #3
  ZONE TYPE PROG
1=Z00  MONITOR
2=Z01  MONITOR
3=Z02  MONITOR
Zones Installed Screen  
  ZONE TYPE PROG
1=MONITOR
2=SMOKE PHOTO
3=WATERFLOW 
Zone Type Program Screen #1  
  ZONE TYPE PROG
1=MEDICAL
2=HAZARD
3=TAMPER
Zone Type Program Screen #3  
  ZONE TYPE PROG
1=SUPERVISORY
2=PROC. MON
3=SMOKE ION
Zone Type Program Screen #4  
  ZONE TYPE PROG
1=HEAT
2=PULL STATION
3=DUCT
Zone Type Program Screen #2