SDM-CD16AC 16 Channel AC/DC Controller 
 
TABLE 1.  Datalogger to SDM-CD16AC Connections 
Connection 
Order 
 
SDM-CD16AC 
 
Datalogger
 (see note) 
 
Function 
First 
12 V 
12 V on datalogger or 
Power 
 
 
external supply  
 
Second Gnd 
Gnd 
Common 
ground 
 C1 SDM-C1 
(CR3000, 
CR5000) or C1 (other 
dataloggers) 
Data 
 C2 SDM-C2 
(CR3000, 
CR5000) or C2 (other 
dataloggers) 
Clock  
 C3 SDM-C3 
(CR3000, 
CR5000) or C3 (other 
dataloggers) 
Enable 
 
On a CR7, SDMs connect to the ports at the upper right corner 
of the 700X Control Module.  On a CR9000X, SDMs connect to 
the ports on the CR9032 CPU Module, and on a CR9000, SDMs 
connect to the ports on the CR9080 PAM Module. 
NOTE 
If the 21X power supply is used to power the SDM-CD16AC, all low level 
analog measurements (thermocouples, pyranometers, thermopiles, etc.) must 
be made differentially.  This is a result of slight ground potentials created 
along the 21X analog terminal strip when the 12 V supply is used to power 
peripherals.  This limitation reduces the number of available analog input 
channels and may mandate an external supply for the SDM-CD16AC. 
4.  Installation 
•  The SDM-CD16AC must be installed in an enclosure that provides a 
pollution degree 2 environment (normally, only nonconductive pollution.  
However, a temporary conductivity caused by condensation may be 
expected).  All Campbell Scientific enclosures meet this requirement. 
•  Use copper conductors only. 
•  Wire Range:  30 − 14 AWG 
•  Tightening Torque: 5 − 7 in./lb. 
•  Use minimum 60/75 degree C wire. 
•  Input power must be connected to a class 2 supply only.  All Campbell 
Scientific power supplies meet the class 2 supply requirements. 
The order in which connections are made is critical.  
Always connect 12 V first, followed by ground, then Control 
Ports. 
CAUTION