Master Programming Level
The Canadian Options configures the FACP with the following as required by Canada:
The following monitor module type codes are not available:
• monitor
• non-latching supervisory
• non-latching drill
• non-latching process monitor
• process monitor
• hazard
• tornado
• medical alert
The auto-silence timer is fixed at 20 minutes and cannot be changed.
Addressable ionization smoke detector sensitivity is automatically monitored using Canadian 
specifications.
Waterflow Silenceable
Pressing 2 while viewing System Setup Screen #3 will allow the programmer to configure the sys-
tem for silenceable on nonsilenceable waterflow circuits.  Each press of the 2 key will toggle the 
display between Waterflow Sil. No and Waterflow Sil. Yes.   When Waterflow Sil. No is selected, all 
output devices associated with a waterflow type input device, will be nonsilenceable.  When Water-
flow Sil. Yes
 is selected, all output devices associated with a waterflow type input device, will be 
silenceable.
3.6.6  Verify Loops
Pressing 3 while viewing Programming Screen #2, will select the Verify Loops option and display 
the following screen:
During loop verification, the FACP polls each device on the selected SLC to determine if the device 
is communicating and whether or not it responds with the proper type identification.  The program-
mer can choose to verify one or both loops by pressing the number corresponding to the choices 
shown above.  
When the selection is made, the following screen will be displayed while verification is in progress:
When Loop verification has been completed, the display will indicate that the system is OK or, if 
problems have been detected, any device type programming errors.  Use the up and down arrow 
keys to view all detected errors.
    PROGRAMMING
1=LOOP SETUP
2=SYSTEM SETUP
3=VERIFY LOOPS
Programming Screen #2
    VERIFY LOOPS
1=LOOP 1
2=LOOP 2
3=BOTH LOOPS
Verify Loop Select Screen
  VERIFYING LOOPS
    PLEASE WAIT