Honeywell MS-9600UDLSE Manual Do Utilizador

Página de 208
MS-9600LS Series Manual — P/N 52646:B2  2/12/2010
117
Master Programming Level
Programming
Pressing 2 for View Points while viewing the Unit In Walktest screen will display one of the follow-
ing screens:
If the system has no points installed, the first screen will be displayed.  If points are installed, the 
second screen will be displayed, which allows the viewing of all untested system points and their 
status relating to the current walktest session.  The up and down arrow keys will allow viewing of 
all untested points.  If a point is tested while it is being displayed, the screen will update and display 
the next untested point.  The first line indicates the total number of untested points.  The second line 
displays information about an untested point.  A description on the bottom of the screen will indi-
cate if the displayed point has been disabled, if the Walktest option has been disabled for that point 
or if the point is not yet tested.  The up and down arrow keys allow the user to scroll through all 
untested points.
Pressing 3 for View Summary while viewing the Unit In Walktest screen will display a new screen 
which will show a total of the tested detectors, tested modules, untested detectors and untested 
modules for the current walktest session.  If more than one SLC loop is installed on the FACP, 
pressing the down arrow key will display the Walktest summary for each SLC loop.
The user can perform a one-person walktest by activating devices throughout the system.  As each 
device is activated, the information about the activated device is stored in the Walktest Log.  The 
information can be viewed by choosing one of the options from the Unit In Walktest screen.
To end the Walktest session, press the Escape key to return to the Walktest screen.  Pressing 3 for 
View Results while viewing the Walktest screen, after a walktest session has been completed, will 
allow the operator to view the final results of the most recent walktest.  The following screen will 
be displayed:
Use the up and down arrow keys to view all of the walktest results which will be displayed.  Note 
that the Walktest log is stored in RAM.  If all power (AC and DC) is removed from the FACP, the 
Walktest log information will be lost.  This information is also overwritten when subsequent walk-
tests are performed.
3.6.9  Option  Modules
Options available for the FACP include ACS, Graphic, LED, Relay and LCD annunciators, printer 
connection for acquiring hardcopy printouts of panel data and PC (Personal Computer) connection 
for uploading and downloading panel data.  
 NO POINTS IN
    SYSTEM
OR
UNTESTED POINTS   010
1D001   SMOKE (PHOTO)
*********************
NOT TESTED
  WALKTEST RESULTS
View Result Screen
    PROGRAMMING
1=HISTORY
2=WALKTEST
3=OPTION MODULES
Programming Screen #3